What is the optimum range to test motor insulation?

I have insulation meter (Megger) up to 5000VDC, what is the optimum range to test insulation of the motor?

If it's a 460V motor, the 1000V range should give a good indication. If the motor is 600 volts or less, 1000 to 2000 volt meggar is sufficient. Higher voltage meggar is fine, but no less than a 1000 volt and be sure the motor is disconnected from the VFD.

Also, reading the great suggestions for load testing your VFD, you might consider using a generator load bank as an alternative. These can usually be rented and are easy to setup and control.

Post a Comment:

    
Plz Calculate (8 * 4) =
(Your comment will show after approved.)

You may also like:

Featured Articles
Non-Enclosure Variable Frequency Drive ... Non-Enclosure Variable Frequency Drive (VFD)No enclosure (cover), reducing installation space and cost effective. Widely used in All-In-One control cabinet. Keep the same ...
Variable frequency drive application ... Variable frequency drive application guideVariable Frequency Drive (VFD) can be used in lots of fields. Variable frequency drives are widely used to control the speed of ...
Variable frequency drive in HVAC ... Variable frequency drive in HVAC systemsVariable frequency drives (VFD) have been used for HVAC systems in buildings for more than 40 years. But only in recent years, ...
Variable Frequency Drive Harmonics and ... A discussion of the benefits of variable frequency drives often leads to a question regarding electrical harmonic distortion ...
Three phase inverters Three phase invertersIn the variable frequency drive rectifier paper, it explains how to go from three phase alternating current voltage to a direct ...
Variable Frequency Drive Service
VFD manufacturers
Variable Frequency Drive Sales Email buy@vfds.org
Variable Frequency Drive Support Email tech@vfds.org